Power Transmitted using Area of X-Section (1-Phase 2-Wire Mid-Point Earthed) Solution

STEP 0: Pre-Calculation Summary
Formula Used
Power Transmitted = sqrt(Area of Underground AC Wire*Line Losses*(Maximum Voltage Underground AC*cos(Phase Difference))^2/(4*Resistivity*Length of Underground AC Wire))
P = sqrt(A*Ploss*(Vm*cos(Φ))^2/(4*ρ*L))
This formula uses 2 Functions, 7 Variables
Functions Used
cos - Cosine of an angle is the ratio of the side adjacent to the angle to the hypotenuse of the triangle., cos(Angle)
sqrt - A square root function is a function that takes a non-negative number as an input and returns the square root of the given input number., sqrt(Number)
Variables Used
Power Transmitted - (Measured in Watt) - Power Transmitted is the amount of power that is transferred from its place of generation to a location where it is applied to perform useful work.
Area of Underground AC Wire - (Measured in Square Meter) - Area of Underground AC Wire is defined as the cross-sectional area of the wire of an AC supply system.
Line Losses - (Measured in Watt) - Line Losses is defined as the total losses occurring in an Underground AC line when in use.
Maximum Voltage Underground AC - (Measured in Volt) - Maximum Voltage Underground AC is defined as the peak amplitude of the AC voltage supplied to the line or wire.
Phase Difference - (Measured in Radian) - Phase Difference is defined as the difference between the phasor of apparent and real power (in degrees) or between voltage and current in an ac circuit.
Resistivity - (Measured in Ohm Meter) - Resistivity is the measure of how strongly a material opposes the flow of current through them.
Length of Underground AC Wire - (Measured in Meter) - Length of Underground AC Wire is the total length of the wire from one end to other end.
STEP 1: Convert Input(s) to Base Unit
Area of Underground AC Wire: 1.28 Square Meter --> 1.28 Square Meter No Conversion Required
Line Losses: 2.67 Watt --> 2.67 Watt No Conversion Required
Maximum Voltage Underground AC: 230 Volt --> 230 Volt No Conversion Required
Phase Difference: 30 Degree --> 0.5235987755982 Radian (Check conversion here)
Resistivity: 1.7E-05 Ohm Meter --> 1.7E-05 Ohm Meter No Conversion Required
Length of Underground AC Wire: 24 Meter --> 24 Meter No Conversion Required
STEP 2: Evaluate Formula
Substituting Input Values in Formula
P = sqrt(A*Ploss*(Vm*cos(Φ))^2/(4*ρ*L)) --> sqrt(1.28*2.67*(230*cos(0.5235987755982))^2/(4*1.7E-05*24))
Evaluating ... ...
P = 9115.04896569727
STEP 3: Convert Result to Output's Unit
9115.04896569727 Watt --> No Conversion Required
FINAL ANSWER
9115.04896569727 9115.049 Watt <-- Power Transmitted
(Calculation completed in 00.004 seconds)

Credits

Created by Urvi Rathod
Vishwakarma Government Engineering College (VGEC), Ahmedabad
Urvi Rathod has created this Calculator and 1500+ more calculators!
Verified by Kethavath Srinath
Osmania University (OU), Hyderabad
Kethavath Srinath has verified this Calculator and 1200+ more calculators!

6 Power & Power Factor Calculators

Power Transmitted using Area of X-Section (1-Phase 2-Wire Mid-Point Earthed)
Go Power Transmitted = sqrt(Area of Underground AC Wire*Line Losses*(Maximum Voltage Underground AC*cos(Phase Difference))^2/(4*Resistivity*Length of Underground AC Wire))
Power Factor using Area of X-Section (1-Phase 2-Wire Mid-Point Earthed)
Go Power Factor = sqrt(4*(Power Transmitted^2)*Resistivity*Length of Underground AC Wire/(Area of Underground AC Wire*Line Losses*(Maximum Voltage Underground AC^2)))
Power Transmitted using Line Losses (1-Phase 2-Wire Mid-Point Earthed)
Go Power Transmitted = sqrt(Line Losses/(2*Resistance Underground AC))*(Maximum Voltage Underground AC*cos(Phase Difference)/sqrt(2))
Power Factor using Line Losses (1-Phase 2-Wire Mid-Point Earthed)
Go Power Factor = sqrt(4*(Power Transmitted^2)*Resistance Underground AC/(Line Losses*(Maximum Voltage Underground AC^2)))
Power Transmitted using Load Current (1-Phase 2-Wire Mid-Point Earthed)
Go Power Transmitted = Current Underground AC*Maximum Voltage Underground AC*cos(Phase Difference)/sqrt(2)
Power Factor using Load Current (1-Phase 2-Wire Mid-Point Earthed)
Go Power Factor = (sqrt(2)*Power Transmitted)/(Current Underground AC*Maximum Voltage Underground AC)

Power Transmitted using Area of X-Section (1-Phase 2-Wire Mid-Point Earthed) Formula

Power Transmitted = sqrt(Area of Underground AC Wire*Line Losses*(Maximum Voltage Underground AC*cos(Phase Difference))^2/(4*Resistivity*Length of Underground AC Wire))
P = sqrt(A*Ploss*(Vm*cos(Φ))^2/(4*ρ*L))

What is the value of volume of conductor material in this US?

The maximum voltage between conductors is vm so that r.m.s. value of voltage between them is vm/√2.

How to Calculate Power Transmitted using Area of X-Section (1-Phase 2-Wire Mid-Point Earthed)?

Power Transmitted using Area of X-Section (1-Phase 2-Wire Mid-Point Earthed) calculator uses Power Transmitted = sqrt(Area of Underground AC Wire*Line Losses*(Maximum Voltage Underground AC*cos(Phase Difference))^2/(4*Resistivity*Length of Underground AC Wire)) to calculate the Power Transmitted, The Power Transmitted using Area of X-Section (1-phase 2-wire Mid-point Earthed) formula is defined as the bulk movement of electrical energy from a generating site, such as a power station or power plant, to an electrical substation where voltage is transformed and distributed to consumers or other substations. Power Transmitted is denoted by P symbol.

How to calculate Power Transmitted using Area of X-Section (1-Phase 2-Wire Mid-Point Earthed) using this online calculator? To use this online calculator for Power Transmitted using Area of X-Section (1-Phase 2-Wire Mid-Point Earthed), enter Area of Underground AC Wire (A), Line Losses (Ploss), Maximum Voltage Underground AC (Vm), Phase Difference (Φ), Resistivity (ρ) & Length of Underground AC Wire (L) and hit the calculate button. Here is how the Power Transmitted using Area of X-Section (1-Phase 2-Wire Mid-Point Earthed) calculation can be explained with given input values -> 9115.049 = sqrt(1.28*2.67*(230*cos(0.5235987755982))^2/(4*1.7E-05*24)).

FAQ

What is Power Transmitted using Area of X-Section (1-Phase 2-Wire Mid-Point Earthed)?
The Power Transmitted using Area of X-Section (1-phase 2-wire Mid-point Earthed) formula is defined as the bulk movement of electrical energy from a generating site, such as a power station or power plant, to an electrical substation where voltage is transformed and distributed to consumers or other substations and is represented as P = sqrt(A*Ploss*(Vm*cos(Φ))^2/(4*ρ*L)) or Power Transmitted = sqrt(Area of Underground AC Wire*Line Losses*(Maximum Voltage Underground AC*cos(Phase Difference))^2/(4*Resistivity*Length of Underground AC Wire)). Area of Underground AC Wire is defined as the cross-sectional area of the wire of an AC supply system, Line Losses is defined as the total losses occurring in an Underground AC line when in use, Maximum Voltage Underground AC is defined as the peak amplitude of the AC voltage supplied to the line or wire, Phase Difference is defined as the difference between the phasor of apparent and real power (in degrees) or between voltage and current in an ac circuit, Resistivity is the measure of how strongly a material opposes the flow of current through them & Length of Underground AC Wire is the total length of the wire from one end to other end.
How to calculate Power Transmitted using Area of X-Section (1-Phase 2-Wire Mid-Point Earthed)?
The Power Transmitted using Area of X-Section (1-phase 2-wire Mid-point Earthed) formula is defined as the bulk movement of electrical energy from a generating site, such as a power station or power plant, to an electrical substation where voltage is transformed and distributed to consumers or other substations is calculated using Power Transmitted = sqrt(Area of Underground AC Wire*Line Losses*(Maximum Voltage Underground AC*cos(Phase Difference))^2/(4*Resistivity*Length of Underground AC Wire)). To calculate Power Transmitted using Area of X-Section (1-Phase 2-Wire Mid-Point Earthed), you need Area of Underground AC Wire (A), Line Losses (Ploss), Maximum Voltage Underground AC (Vm), Phase Difference (Φ), Resistivity (ρ) & Length of Underground AC Wire (L). With our tool, you need to enter the respective value for Area of Underground AC Wire, Line Losses, Maximum Voltage Underground AC, Phase Difference, Resistivity & Length of Underground AC Wire and hit the calculate button. You can also select the units (if any) for Input(s) and the Output as well.
How many ways are there to calculate Power Transmitted?
In this formula, Power Transmitted uses Area of Underground AC Wire, Line Losses, Maximum Voltage Underground AC, Phase Difference, Resistivity & Length of Underground AC Wire. We can use 2 other way(s) to calculate the same, which is/are as follows -
  • Power Transmitted = Current Underground AC*Maximum Voltage Underground AC*cos(Phase Difference)/sqrt(2)
  • Power Transmitted = sqrt(Line Losses/(2*Resistance Underground AC))*(Maximum Voltage Underground AC*cos(Phase Difference)/sqrt(2))